Louvre Model | VI Series | ||
 Blade Configuration | Double | ||
 Blade Spacing | 50 mm | ||
 Blade Depth | 65 mm | ||
 System Depth | 180 mm | ||
 Front Blade  Orientation | Mesh | ||
 Rear Blade Orientation | Vertical | ||
 Rain  Defence  Class
AIRFLOW VELOCITY IN M/S |
AIRFLOW VELOCITY IN M/S |
0.0 | A |
0.5 | A | ||
1.0 | A | ||
1.5 | A | ||
2.0 | A | ||
2.5 | A | ||
3.0 | C | ||
3.5 | D | ||
 Airflow Coefficient* | 0.141 | ||
 Airflow Class | 4 | ||
 Rain Defence Rating | Excellent | ||
 Airflow Rating | Fair |
* Alternative Airflow Co-efficients are available for panels larger than 1 m x 1 m
Derived from 3rd party independent testing to BS EN 13030:2001